Open style isolation transformer KKSA
Produktnummer:
Medical isolation transformers have been manufactured with strengthened isolation. The transformers’ leakage current between the primary and secondary windings is very low.
Medical isolation transformers are isolation transformers for earthed devices used in medical facilities. The transformers isolate and separate the connected device from the medical facility’s isolated electric power network. In addition, the transformers keep the leakage current of the devices within the limits set for medical devices.
The maximum leakage current without load at rated voltage and frequency is 0.5mA. There is an electrostatic shield between the primary and secondary windings.
A transformer used in a medical facility must be equipped with an insulation monitoring device. Additional information about these devices can be found in the Trafox Superintend® IMD website. Fault current monitoring systems can be found in the Trafox Superintend® RCM website.
Download specifications
Name | Value |
---|---|
Primary winding | 230V |
Secondary winding | 2x115V |
Power | 3500…7500VA |
Frequency | 50/60Hz |
Protection class | IP00 |
Isolation voltage | 3.5kV |
Insulation class | F(155°C) |
Ambient temperature | -20…+45°C |
Standards | EN61558-1, EN61558-2-15, EN60601-1 |
Mounting | Screw mounting |
Accessories | Current transformer, temperature sensor and switching current attenuation circuit, insulation level monitoring device |